Application
This transmitter is designed to fit Rochester model 6342 and 6360 Magnetel® Float gauges with 8″ dials.

General Information & Features
The model R6315-12 transmitter utilizes electronic circuitry to provide a current output of 4-20 mA, which is proportional to the liquid volume in a horizontal cylindrical storage tank. Transmitter should be used with intrinsically safe voltage input from a loop-power supply and safety barrier.

Documents
Data Sheet
DS-1445 Installation Instructions
DS-873 Mounting Instructions



一般规格 *

4-20 mA output, 36” wire length.
24 VDC input.
Conformity ±1.5%.
Load: 495 ohms or less.
UL Listed as intrinsically safe.

五金件 *

Studs 1/2-20, 0056-00496, 2 each
Jam nuts 1/2-20, 0044-00406, 4 each
Stand-off post, 0070-00015, 3 each
1/2” seal-tite connector is integral to transmitter

WARNING! This sensor is not to be used as the primary means of determining high or low fuel condition. It must not be used in the absence of redundant systems in critical applications where there may be significant safety risk or financial exposure in the event of fuel overfill or fuel exhaustion condition. This sensor is not to be used for tank filling.

注意:

1. 在电源线上添加的总电阻应小于495欧姆, 以便在25.5 伏的情况下正常工作, 这对于大多数屏障来说是内在的安全限制。

2. 数字液位指示器不能使用或生成超过 250 vac。

* 材料和规格如有更改, 恕不另行通知。压力额定值可能会因温度和其他环境因素而发生变化。